CHAPTER VII

REQUIREMENTS OF SIGNALLING

SECTION 'A'

Signals, Generally

7.1 Location of Signals :-

7.2 Size of Lenses :- The lenses of subsidiary signals shall be of smaller diameter than those of running signals. Subsidiary signal shall not be brighter than the running signal.

7.3 Number of Signals and height :- The number of signals and their height shall be limited to what is necessary for safety and operational requirements.

7.4 Outside interference :- All apparatus shall be so designed ,located and secured as to obviate, as far as possible, outside interference.

7.5 Signals controlled through slots and disengagers :- Where a signal is controlled though slot or disengagers, it shall not be possible to take 'off 'a signal unless all the controls have been exercised by by the controlling agencies. It shall be possible for any one of the controlling agencies to replace the signal to 'ON' position by withdrawal of the control.

7.6. Standard and type of signalling on a section. : It is desirable that the signalling at all block station and interlocked level crossing in the same section conform to same standard and type.

7.7 Visibility. : The minimum visibility distance of various signals shall be as under-

Two Aspect Signals-

Note : Where adequate visibility of stop signals cannot be provided, repeater or co-acting signals shall be provided to ensure the combined visibility or speed restrictions imposed.

Multiple Aspect Signal

SECTION  'B'

Semaphore Signals

7.8 Visibility of a Signal from the place of operation. : Where a Signal ,due to its position is not visible to the Railway servant operating the signals, the aspect of Signal and the condition of its light shall be repeated at the place of operation. Repeater for the Home Signal and the Last Stop Signal shall be provided in the station Master's office also if all the following conditions are fulfilled-

7.9 Visibility of front light- Where the front light of the signal is not visible from the place of operation a back light or a repeater shall be provided. The back light shall show a white light in on position and no light in any other position .

7.10 Fixed Green Light of Warner Signal- The fixed green light above a Warner Signal on a post by itself shall be provided with a back light or it shall be repeated.

7.11 Unworked Warner Signal- The position of the arm of unworked Warner Signal which is not visible , need not be repeated .The condition of the light shall, however ,be repeated.

7.12 Back lights for the 'Attention' aspect. : The arrangement for the back light for a Signal capable of displaying the attention aspect shall be such that two lights are visible in the 'ON 'position and no light in any other position. However, only back light of the Main yellow aspect may be provided for electrically lit Distant Signals, if arrangement is such that the bottom light is lit only when the arm is displaying the attention aspect.

7.13 Fixing Signal arms. : All signal arms shall be fitted on the left hand side of the post.

Two Aspect Lower Quadrant Signalling-

7.14 Warner Signals-

7.15 Stop Signals-

7.16 Stop Signal -Location of -

7.17 Distinction between Signals- For diverging lines-

7.18 Distinction between Signals -For converging lines -when two or more lines converge ,the signal shall be fixed on separate posts .Where signals are carried on brackets or bridges under approved special instructions, instruction given in para 7.17.3 will apply.

Subsidiary Signals

7.19 Calling-on Signals-

7.20 Shunt Signals-

7.21 Repeating Signal-

7.22 Co-acting Signals- Co-acting signal are duplicate signal fixed below stop signal and are provided where , in consequence of height of signal post or of there being an over bridge or other obstacle ,the main arm or light is not in view of the driver during the whole time that he approaching it. Co-acting signal shall be fitted at such height that either the main arm or light or Co-acting arm or light , is always visible.

Modified Lower Quadrant Signalling

7.23 Provision -Modified lower quadrant signalling shall be provided only under special instructions issued by Railway Board .Where the provision of such signalling is permitted , the requirement laid down on this section shall apply.

7.24 Distant Signals-

7.25 Warner Signal-

7.27 Stop signals. : Location of-

7.28. Distinction between signals :- Requirement shall be same as indicated in paragraphs 7.17 and 7.18.

7.29. Subsidiary signals :- Requirement shall be as in Paragraphs 7.19 to 7.22.

Multiple Aspect Semaphore Signalling

7.30.

7.31 Stop signals:

7.32 Stop signal - Location of -

7.33 Aspects. : Sequence-

7.34 Combined signals. : When owing  to their location, it is necessary to combine two signals, one stop signal only may be provided under approved special instructions, capable of displaying any or all of the following aspects:-

7.35 Distinction between Signals. : For diverging lines- Requirements shall be as in para 7.17.1 to 7.17.3.

7.36 Distinction between signals- For converging lines- Requirements shall be as in para 7.18.

Subsidiary signals

7.37 Calling on signals-

7.38 Shunt signals-

 SECTION 'C'

Colour light signals

7.39 General-

7.40 Aspect of signals-

7.41 Route indicator-

The type of route indicator to provided instead of separate signal shall be as under-

7.42 Subsidiary signal-

 SECTION 'D'

 Gate signals

7.43 A gate stop signal shall be fixed at a adequate distance from the gate ,this adequate distance not being less than the value stipulated in Para7.45.1 and 7.45.2.

7.44 The gate stop signal be provided with 'G' marker except where prohibited under special instructions.

The 'G' marker shall consist of letter 'G' in black on a yellow disc. T he instruction in para 7.168.2 shall apply to signal protecting level crossing gate s in automatic block territory.

7.45  Interlocked level crossing gates out side station limits

7.46 Interlocked level crossing gates insides station limits or on the vicinity-

SECTION 'E'

Warning Boards

7.47 A warning board to warn the driver of his approaching to stop signal shall be provided at a distance of 1.4 km. in rear of first stop signal of a station and gate stop signal. This distance may be increased suitable to cater for gradient .

7.48 On sections where emergency breaking distance of more than 1.6 km. has to catered for,

a second approach signal shall be provided failing which suitable speed restrictions imposed.

7.49 In cases where gate signals and station signals happen to be located close to each other, only one warning board shall be provided at distance of not less than 1.4 km. from the first stop signal.

7.50 Where inter signal distance between two signals is less than the distance required for warning board, the signal in rear shall either be controlled by the signal in advance or they shall be combined.

7.51 Self reflecting sheets of approved type or reflector shall be on the warning board as per approved drawings.

7.52 The warning boards shall be normally be on the left of the line to which it applies unless their are special reason to the contrary.

SECTION 'F'

Indication boards

7.53 Indication boards are provided to give warning to drivers about changes in type of signalling or type of block working.

7.54 Where a block station ,which is provided with two aspect signalling , without warner signal in rear of first stop signal, is approached from a section provided with multiple aspect signalling or two aspect signalling with a warner signal in rear of first stop signal, an indication board bearing alternate yellow and black diagonal stripe shall be fixed at not less than 1.4 km. in rear of first stop signal. The board shall have a legend "Approach unwarned stop signal".

   7.55. When a station is provided with single line token block is approached from a double line or a single line section equipped with tokenless block working ,an indication board with symbol "Entering token territory "shall be provided at the first stop signal of the station.

7.56. Where the block working at one end of station is automatic and other end is absolute ,an indication board with suitable legend shall be at the first stop signal of the station.

The legend of the board shall be "Entering absolute block territory" or "Entering automatic block territory" as appropriate.

7.57. Shunting Limit Board : A shunting limit board shall be provided at class 'B' station over a single line section worked on absolute block system where shunting in the face of approaching train is permitted and and where a advance starter is not provided . The shunting limit board shall fixed at a distance of not less than 400 meters in the case of two aspect lower quadrant signalling territory and 180 meters in case of multiple aspect and modified lower quadrant signalling in advance of first stop signal.

7.58. Block and Section Limit Board:-

7.59. The block section limit board or shunting limit board shall be located that the legend is facing towards the station. They shall be fitted with lamps showing white light in the both directions during night.

Note: Chapter XII may be referred to for painting details.

SECTION 'G'

Points

7.60 All double wire worked points and lock mechanism shall be provided with broken wire locks and electrical detection in addition to mechanical detection. In the case of point mechanism ,the broken wire broken wire lock shall function before opening between stock rail and tongue rail exceeds 5 mm. at 150 mm. from the toe.

Note : In all new installation, points, locks ,and bars shall not be operated by wire but by rodding or by electrical means.

7.61. Permissible distances. :  The distance at which points may be worked by rodding must not exceed 320 meters except where the stroke at the lever tail is not less than 200 mm. in which case the above distance may be increased to 460 meters . For special type of switches, the Chief Signal and Telecommunication Engineer may stipulate the permissible distance.

Note : No new installation shall be commissioned with point mechanically operated and locked by the same lever.

7.62 . Obstruction test- The insertion of 5 mm. obstruction between the switch rail and stock rail of facing point, approximately 150 mm. from the toe of switch shall prevent the point from being locked and relative signal or signals, where provided, being taken 'OFF' for movements in the facing direction.

7.63 Detection by shunt signals-

7.64 Operation of facing point lock- The operation of  facing point lock shall depend on the correct operation of lock bar. This lock bar shall form a part of transmission and be in series with it .

7.65. Length of lock bars- The length of lock bar shall exceed the greatest distance between any two adjacent axles of any vehicle likely to be used on the section.

7.66. Point indicators-

7.67. Trap indicators-

7.68. Size of lights and placing. : Points and trap indicators shall be provided with miniature lights and as a rule be placed as closed to ground as circumstances permits.    

7.69. Shunting permitted Indicator :-

Indication when shunting is permitted in the direction to which it refers

Indication when shunting is permitted in the direction to which it refers

Day indication

Night indication

Day indication

Night indication

Disc type

Black disc with a yellow cross painted on it

Yellow cross light

Edge of disc

No light

Light type

Yellow cross light 

Yellow cross light

No light

No light

7.70. Spring Points:-

7.71. Movable Diamond Crossing :- Movable Diamond crossing on passenger lines shall be provided by complete facing point equipment of approved type .

7.72 Means of Isolation :

7.73. Provision of Isolation-

7.74. Arrangements of Sidings. : Sidings shall be so arranged that shunting operations upon them involve the least possible use of, or obstruction, to running lines.

Siding Points on Passenger running lines outside station limits

7.75. Facing Points (Single Line) :

7.76. Facing Points (Double Line) :The minimum equipment for Points taking off a running line in the facing direction on Double Line shall be in accordance with the provisions of the Para 7.75.

7.77. Trailing Points (Double Line) :Where Points take off a running line in a trailing direction the following minimum equipment shall be provided for unrestricted speed:-

SECTION 'H'

Signal Cabins and Interlocking

7.78. Location and elevation of cabins.- Signal cabins shall be so located, elevated and built as to provide the Operator with sufficient space and to enable him to have an adequate view of signals operated from the cabin as well as of the movements taking place in the portion of the yard controlled by him unless a substitute for direct vision is provided.

7.79. Cabin equipment:-

7.80. Numbering of levers. : All levers, including spares, shall be numbered consecutively through the frame from left to right. Each lever shall be provided with a number plate. This will show the function in the order of operation which must precede to release when no lever description board is provided.

7.81. Signal and interlocking apparatus. : Installation. : Signal and interlocking apparatus shall be as far as possible, so installed and the connections and circuits so arranged, that the relevant fixed signal shall remain at or return to its most restrictive aspect in the event of failure of any part of its connection and circuits.

7.82. Essential of Interlocking. : Lever frames and other apparatus provided for operation and control of signals, points, etc., shall be so interlocked and arranged as to comply with the following essentials:-

7.83. Holding Route :-

7.84. Locking trailing points by S signals in advance :-Levers operating Stop Signals which are next in advance of trailing points operated from the same cabin, shall when reversed, lock such point levers in either position unless route locking is provided or the distance between the points and the signal is such that the locking interferes with traffic movement.

7.85. Clearance at Junction Point :-

7.86. Track Circuit Control of Signals. : Where continuous track circuiting is provided, the occupation by a vehicle of any track circuited section shall control the running signal or signals leading to the same line and shall also lock in either position, the Points on the section.

7.87. Slot Circuits. :Slot circuits for Home Signals leading to non-track circuited receptions lines shall be so arranged that slot once given is effective for the reception of only one train and a fresh slot has to be given for a subsequent train.

7.88. Station Master's Control-

7.89. Interlocking of Last Stop Signal and First Stop Signal with Block Instrument.- Where Block instruments are in use

7.90. Automatic replacement of Signals:

SECTION 'I'

Interlocking of Catch Sidings and Slip Sidings

7.91. At station where Catch and Slip Sidings are provided in accordance with the Rules for the opening of a Railway, interlocking arrangements and other safeguards in accordance with Paragraphs 7.92 to 7.97 shall be provided.

7.92. Reception of trains :

7.93. Setting of Catch Siding/Slip Siding :- The take off points of a Catch/Slip siding shall normally be set and locked for the siding and interlocking between the points and block instruments shall be provided as in para 7.94 and other safeguards as in paragraph 7.95 to 7.97.

7.94. Interlocking of Catch/Slip Siding points with Block Instrument. : The interlocking shall be such that the key required to set the siding points is released from the instruments in the "Train Going to" / "Train Coming from" position and once the key is removed from the block instrument, the instrument gets locked in the relevant position. The instrument can be normalised only after the points are set for the the Slip Siding/Catch siding and the "Train Going To" / "Train Coming from" key is released from the Points and brought back to release the instrument. Where a Slip Siding is located at the departure end of a Double Line Station, the interlocking shall be such that the Points can be set towards the Block section only when the block instrument is set to :Line Clear".

7.95. Audible Indication. : An audible indication shall be provided at the place of operation of Points as an aid to the Operating staff, indicating that the train has been received or despatched and that the points shall now be reset for the Catch Siding/Slip Siding. This indication would continue till the points are reset for the Catch Siding/Slip Siding.

7.96. Safeguards in working. : In all cases where interlocking arrangements stipulated in para 7.94 are provided between the Slip/Catch Siding and the block instrument, the following safeguards shall also, inter-allia be provided in the Station Working Rules :-

7.97. Emergency Key. : An Emergency Key of the Catch/Slip Siding shall be kept in a sealed box under the custody of the Station Master. This is used for operating the Slip Siding/Catch Siding points when either the block instrument have failed, or when the train is still in the Block section and a train is required to be despatched into the Block section.

SECTION 'J'

 Operating of Points and Signals by Electrical Means

7.98. The points and Signals may be operated individually from a -

7.99. Locking and sealing arrangements.- Locking and sealing arrangements shall be provided for the covers of locking tray frame/power frame, etc., to secure against unauthorised opening.

7.100. Lever frame/ Power frames.-

7.101. Operation of Signals by Electrical means. : Where levers are used to operate signals by electrical means, they shall be provided with "normal" indication locks adapted directly to prevent the full return movement of the lever to the normal position unless the signal has returned to the 'ON' position. This rule does not apply to a mechanical interlocking frame if

7.102. Operation of points by Electrical means. : Except where alternative electric locking is provided, the lever operating electrically worked points shall be provided with "normal " and " reverse " indication locks adapted directly to prevent the full movement of the lever, unless the point mechanism has made the required movement and the points are set and locked in a position corresponding to that of the lever and in the case of facing points, they are securely locked.

7.103. Visual indicators shall be provided to show the "normal" and "reverse " position of all points the condition of all track circuited sections, route setting and to repeat the indications of Colour Light Signals.

7.104. Track circuits as a means for detecting obstructed lines. : Adequate arrangements shall be made, where necessary for reminding the Operator of vehicles which are standing within his control. In case of passenger lines or where light engine crossing and shunt movement are frequent or where stop Signals are at a considerable distance from the Cabin, or where the view of the Operator is likely to be obstructed, the provision of track circuits or other automatic device is desirable.

7.105. Track Circuiting.- At Stations where points and signals are operated from an Assistant Station Master's Office at a central place, track circuiting of the entire station section including all lines where direct reception is provided shall be done.

7.106. Circuits.-

7.107. Crank Handle Interlocking.-

SECTION 'K'

 Relay Interlocking Installations : Route Setting Type

7.108. Route setting shall be on the basis of "Entrance-Exit" principle. Facility for individual operation of points shall also be provided.

7.109. Route setting, i.e., setting and locking of the route and clearing of main signals include the following processes:-

7.110. The system shall be so designed that the points in a route once set shall remain in the last operated position until they are required to be operated for the setting of another route or for individual operation except when stipulated otherwise.

7.111. the route shall ordinarily be released by the passage of the train over the route . Sectional Route Release may be provided where necessary. Emergency route release shall also be provided with appropriate time delay.

7.112. Approach locking and back locking shall be provided for all routes governed by main signals. Approach and back locking shall be continuously effective from the approach track which shall commence from an adequate distance in rear of the signal.

7.113. Point Operation:-

7.114. Where required provision may be made for emergency sub-section route release. Where such release is provided, it shall be possible to release the sub-section only with the cooperation of both the Station Master and the Maintainer.

7.115. All running signals shall be colour light multi-unit type and shunt signals shall be of the Position Light type. Calling-on signals may be provided in accordance with para 7.19.

7.116. A signal in the 'OFF' position shall be replaced to 'ON' position automatically by the passage of a train. It shall also be possible to replace a manually controlled signal in the 'OFF' position to the 'ON' position manually.

7.117. The Calling-on Signals shall lock and detect points in the Route and prove that the level crossing gates in the Route are closed and locked against road traffic.

7.118. Shunt movements shall, as far as possible, be controlled by Shunt Signals. The Shunt Signals shall lock and detect the points in the Route and prove that the tracks in the route excluding the berthing track are clear and that the level crossing gates in the Route are closed and locked against the road traffic.

7.119 Where local control panels are provided over a portion of the yard, the points and signals of that portion of the yard shall be operated as follows :--

7.120 Suitable indications shall be provided on the control panel for points, track sections, routes, signals including Calling-on Signals, 'A' Markers, level crossings, train approach, power supply cancellation, slot and crank handle interlocking, etc., as required.

SECTION 'L'

Requirements of Signalling Circuits using Electronic Equipment

The following fail-safe principles shall be incorporated in the design of the equipment :--

7.121 Component failure shall be self-detecting by way of causing a signal to display a most restrictive aspect as far as possible.

7.122 Failure of components which are not self-detecting shall not cause any unsafe failure of the equipment. Even simultaneous failures in different components which are not self-detecting shall not cause any unsafe failure of the equipment.

7.123 All fail-safe circuit shall work on continuous energisation principle such that open circuits in wiring, relay contacts, etc. or loss of power supplies shall not cause unsafe conditions.

7.124 Common return shall not be used for vital circuits. In vital circuits, the final stage shall use fail-safe signalling relays. A transformer isolation shall be provided between the final stage fail-safe signalling relay and the electronic device preceding it. The D.G. power supply shall not have any galvanic connection with the coil of the final stage signalling relay.

7.125 All electronic equipment shall have a long Mean Time Between Failures (M.T.B.F.). Duplications of components and parts of equipment or modules can be resorted to for improvement of the reliability where necessary. Where components/parts modules are duplicated, it is desirable that provision may be made for cross checking the performance of one set by the other set and vice-versa.

7.126 Due consideration shall be given to the effects of faults in fail-safe electronic equipment to allow open or short circuit or earthing conditions and variations in component values due to aging, replacement of component with new components with specified tolerance, etc. Safety shall not be impaired as a result of multi-terminal devices failing-either open circuit, short circuit or with partial short circuit between any pair of terminals or earthing.

7.127 Special care shall be taken in the design of amplifier circuit to eliminate the possibility of self-oscillation. It is desirable that loss of safety requirements is not caused should the amplifier go into self-oscillation due to any unforeseen contingency.

7.128 Where specific frequencies are used for safety circuits, particular care shall be taken to ensure that the frequency generating equipment is producing only the desired frequency signal. Verification shall be carried out using passive tuned filters in series with each frequency source.

7.129 The physical construction of fail-safe equipment shall be designed to eliminate the possibility of external objects causing short circuits between combinations of terminals in vital circuits. This may be achieved for example, by adequate separation of terminals, and by the fitting of protective shrouds where necessary.

7.130 For the consideration of the fail-safe feature of an electronic safety signalling device, failure of one component for all the modes of probable faults indicated in paragraph 7.126, one at a time shall be considered. If the failure of the component under examination is not self-detecting, then simultaneous failure of other associated components shall be considered.

SECTION 'M'

Standards of Signalling and Interlocking

7.131 Broad Gauge lines on Indian Railways have been classified into five categories and Meter Gauge lines into four categories in terms of Paragraphs 210 & 211 of the Engineering code. The complement of signalling equipment to be provided at stations on these routes is indicated in the Tables below :--

BROAD GAUGE

* When the suburban section falls under Group 'A', 'B', or 'D', as the case may be, the requirements of that group shall be applicable.

! On Single Line, when density is less than 20 trains each way, Tokenless Block Instrument may provided. On Double Line when density is less than 30 trains each way, Double Line Block Instrument may be provided.

!! If the traffic density is likely to exceed 18 trains each way on single line and 20 trains on double line, Colour Light Signals may be provided.

!!! If the traffic density is likely to exceed 18 trains each way, Tokenless Block Instruments shall be provided and if it exceeds 25 trains each way, Block working shall be by Track Circuit.

!!!! If the traffic density is likely to exceed 30 trains each way, Block working shall be by track circuits.

@ On routes where speed is more than 50 KMPH, Signalling requirements as per Group 'D' shall apply.

METRE GAUGE

*When the Suburban Section falls under Group Q, R1, or R2 / R3, as the case may be, the requirements applicable to the Group shall be provided.

SECTION 'N'

BLOCK INSTRUMENTS

General Requirements

7.132 Construction and Type :

7.133 Lightening Discharger-- All instruments shall be provided with lightning discharger to approved specification. When a line wire is used, lightning discharger must be installed on both wires.

7.134 Prevention of irregular operations. : There shall not be any opening giving access to the interior of the instrument through which it is possible to operate the mechanism by any irregular means.

7.135 Locking and sealing facilities.-- Facilities shall be provided for locking and sealing the instruments. The doors of the instruments giving access to the internal mechanism shall be provided with a double lock, the key of one of which shall be in the custody of the Station Master on duty and the key of the other with the Electrical Signal Maintainer in charge of the maintenance of the Block Instruments. It shall not be possible to open the door of the Block Instruments without the co-operation of both the agencies.

7.136 Prevention of unauthorised operation. : A lock or other device shall be provided to enable the Station Master on duty to prevent unauthorised manipulation of the instrument during his absence.

7.137 Isolation of telephone circuit. : Telephone instrument shall be provided in conjunction with block instruments. It is desirable that the condenser or other means provided for isolating the telephone circuit from the instrument circuit is located within the instrument or in such a way as to be inaccessible for outside interference.

7.138 Bell push. : A bell push button or a bell plunger shall be provided on the instrument for exchange of bell code.

7.139 A separate battery shall be used for each Block Instrument. The battery shall only feed the Block Instruments and not any other circuits. The battery housing shall be locked and sealed.

7.140 Tokenless Block Instruments worked on physical conductors shall be worked on metallic return circuits.

Special requirements of Single Line Block Instruments

7.141 Fixed Indications.-- The instruments shall be provided with visual indication clearly giving the following indications :--

7.142 Current Indicator.-- An indicator, indicating the polarity of the current, shall be provided to indicate incoming and out going line currents.

7.143 Operation:

7.143.1 "Train Going To" and "Train Coming From"-- The instrument shall be such that the co-operation of the Station Master at the other end of the station shall be necessary. Even with the co-operation of the Station Master at the other end, the Station Master has to go through one or more definite moving operations on the instrument in addition to working of bell plunger--

7.143.2 "Line Closed" -- Both the instruments shall be restored to normal before a further operation of setting the instrument to "Train Going To" / "Train Coming From" can be carried out. It shall not be possible for the instruments at either end of the section to be restored to normal without the co-operative features indicated in para 7.143.1

7.144 Operation of "Line Clear" receiving and granting mechanism. : It shall not be possible for r the mechanism which permits a "Line Clear" to be received and that which permits a "Line Clear" to be granted to be in operation at the same time.

7.145 The instruments that is set to "Train Going To" for initiating a train movement shall be the first one to be restored to "Line Closed" on complete arrival of the train at the receiving station.

7.146 Extraction of token-- It shall be possible to extract one token only when the instrument has been set to " Train Going To". It shall not be possible to change the "Train Going To" condition untill the token has been inserted in one of the instruments of the Block section.

7.147 Token instruments shall be so installed that a token of one block section can not be placed in the instrument of an adjacent section and preferably such that if the token is over carried, it can not be placed in an instrument at the next station .

7.148 The tokens of each section shall be engraved with the code name of the stations at both ends of the block section and with a serial number.

Special requirements of Single Line Tokenless Block Instruments

7.149 Fixed Indications --In addition to the fixed indications specified in paragraph 7.141 the instrument shall be provided with means to indicate "Train On Line" at both sending and receiving stations when a train has entered the block section.

7.150 Immunity from extraneous currents.-- Single Line tokenless block instruments shall work on coded impulse/frequency modulated current system so as to be immune from the effects of extraneous currents.

7.151 Operations --Handle type tokenless Block instruments:

7.152 Operations. : Push Button Tokenless Block Instruments :

7.153 Operation of "Line Clear" receiving and granting mechanism. : It shall not be possible for the mechanism which permits a "Line Clear" to be received and that which permits a "Line Clear" to be granted to be in operation at the same time.

7.154. : Tokenless block instrument shall be provided with --

Special requirements of Double Line Block instruments

7.155 Indicators for Up and Down Lines. : The instruments shall be provided with Visual indicators separately for Up and Down Lines to show the following three conditions :--

7.156 Current Indicator-- The indicators provided as per paragraph 7.155 may also serve as the current indicators.

7.157 Operation before granting or receiving Line Clear -- The instrument shall be such that the Station Master has to go through one or more definite moving operations on the instrument besides working the bell or plunger before he can grant Line Clear.

7.158 Audible Indicator-- When required, the instruments may be provided with audible indicators --

7.159 Non-Co-operative type instruments-- Non-Co-operative type double line block instruments shall work on a system of coded currents.

7.160 The requirements indicated in paragraphs 7.155 and 7.158 will apply to these instruments. In addition, take following shall be provided in these instruments:--

7.161 Use of track circuits for proving block section to be clear-- On sections where use of track circuits for proving the block section to be clear is to be introduced, the following equipments shall be provided--

SECTION 'P'

Automatic Signalling

7.162 Automatic Block System on Double line --- Automatic Block is a system in which the movement of trains is controlled by Stop Signals which are operated automatically by the passage of trains past the Signals. No automatic signal shall assume 'OFF' aspect unless the Line is clear not only upto the Stop Signal ahead but also for an adequate distance beyond it. Except under approved special instructions, this adequate distance of overlap shall not be less than 120 metres.

7.163 Automatic and Semi-Automatic Stop Signals on Double Line:--

7.164. Automatic Block System On Single Line:

7.165. Manual and Automatic Stop Signals On Single Line:

7.166. Track circuits:

7.167. Track Indicator For Automatic Signalling On single Line. : A track indicator shall be provided at each station to indicate whether the block section is occupied or not.

7.168. Markers:

7.169. Provision In Graded Section :

7.170. Points and Crossing In Automatic Block Sections.-- Emergency Cross-overs and siding points in trailing direction shall be secured and locked in the normal position and the switches detected by signals reading over the points. In addition, the points shall preferably be approach locked. Cross-overs or points in the facing direction shall be provided with the equipment stipulated in para 7.131 and shall be interlocked with signals which shall be approach locked.

SECTION 'Q'

Centralised Traffic Control

7.171. On sections where centralised traffic control (C.T.C.) is to be installed, the following equipment shall be provided :-

7.172. centralised Traffic Control machine--

7.173. Relay inter locking at way stations:-

7.174. Block Working.- System of block working shall be Automatic Block for Single Line or Double Line, as the case may be. Where electric switch locks are provided on manually operated points in the block section, arrangement shall be such that the electric lock can be unlocked only after an adequate time interval after the relevant signals have been restored to 'ON'.

7.175. Code System and medium for transmission of control and indications;

7.176. Communication Facilities:-

SECTION 'R'

Additional Requirement in 25 kv. 50 cycles A.C. Electrified Sections

7.177. The signalling and telecommunication equipment in a.c. electrified areas is affected by the Electric Traction system in the following manner;-

7.178. Detailed requirements in 25 kv. 50 cycles A.C. electrified areas are enumerated in part II.

Special requirements for Block Instruments

7.179. Block Instruments shall not be worked on overhead lines. They shall be connected to underground cables as per approved drawings.

7.180. A block filter of an approved design shall be installed the Single or Double Line Block Instrument and the Cable Conductors.

7.181. When a block section originates at a station in electrified area and terminates at a station in non-electrified area, Block instruments at both ends of such block section shall be provided with block filter in accordance with approved instructions.

7.182. The block telephone of Single or Double Line Block instruments shall not be worked on the same cable conductor as the block instrument. It shall be worked on a separate pair of cable conductors.

7.183. Over single section, only approved type of Token and Tokenless Block Instruments shall be used. If the length of parallelism dose not exceed 1.5 Kilometres, Push Button Tokenless Block Instruments may be used.

7.184. Over Double Line Sections, only approved type of Block Instruments with block filters shall be used. Details of type of instruments to be used are enumerated in Part II.

 

previous          next